首页> 中文期刊> 《国防科技大学学报》 >爆磁压缩发生器延时控制系统分析及实现

爆磁压缩发生器延时控制系统分析及实现

         

摘要

针对爆磁压缩发生器高精度延时起爆控制的要求,建立了基于电路控制延时方案的最佳起爆时序模型,分析了其时序误差散布。设计了一种爆轰驱动飞片型高功率放电开关,通过数值仿真分析了开关的耐压能力及飞片变形。实验测试了6发开关的闭合放电性能,数据表明:开关两极间电压5 kV时未出现击穿现象,闭合响应时间分布在66±5μs以内、标准差2.7μs,开关导通时间≥900μs,放电效率接近90%。采用小型爆磁压缩发生器与延时控制系统进行了联调实验,结果表明:爆磁压缩发生器运行时刻与电流峰值时刻相差1.8μs,延时误差7.8%,延时控制系统满足高精度起爆控制的要求。%Time-delay control system is very important to magnetic flux compression generator’s operation.Based on circuit delay scheme,an appropriate model was built to analyze the initiation time sequence,and its errors dispersion was analyzed.A switch driven by detonation was proposed,its voltage endurance capability and plate deformation were analyzed by simulation.On this basis,six switches were tested at high voltage.The data shows that,there is no voltage breakdown at 5kV,response-time distributes in 66 ±5μs with standard deviation of 2.7μs, conducting time is equal or greater than 900μs,discharge efficient is approximately equal to 90%.A mini-type magnetic flux compression generator was used to test the time-delay control system and the results show that,the time difference between magnetic flux compression generator’s operation and current peak is only 1.8μs with the error being 7.8%.

著录项

相似文献

  • 中文文献
  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号